Brazilian Archives of Biology and Technology2024
Development of a Low-Energy Mobile Current Waveform Impulse Generator for Application in Low Voltage Surge Arresters
Tiago Goncalves Zacarias, Rafael Martins, Carlos Eduardo Xavier, Júlio Cezar Oliveira Castioni, Germano Lambert-Torres, Frederico de Oliveira Assunção, Levy Ely de Lacerda de Oliveira, Carlos Eduardo Teixeira, Luiz Eduardo Borges da Silva e Erik Leandro Bonaldi
em inglês
resumo
Abstract Surge arresters are at the forefront of protection against voltage surges. The loss of the protective effect of surge arresters imposes accidents and unplanned shutdowns on the power system. It directly affects the interruption of power supplies and imposes fines on service providers. Monitoring and diagnostics in the lightning rod field require studies and work that present the degradation behaviour of surge arresters to help develop and improve existing techniques. This paper presents the development of a laboratory with a low-energy, mobile current waveform impulse generator. It allows for conducting aging tests by applying discharges to low-voltage zinc oxide surge arresters used in the energy distribution sector. Samples of surge arresters were subjected to the discharges produced by the developed generator, and they exhibited degradation, thus showing asymmetry between the positive and negative half-cycles of leakage current.
como citar · ABNT NBR 6023
ZACARIAS, Tiago Goncalves et al. Development of a Low-Energy Mobile Current Waveform Impulse Generator for Application in Low Voltage Surge Arresters. Brazilian Archives of Biology and Technology, 2024. DOI: 10.1590/1678-4324-2024230669.
Referências
36 obras citadas
- 1J He, J Lin, W Liu e mais 3. Structure-Dominated Failure of Surge Arresters by Successive Impulses. IEEE TransPower Del, 2017quem mais cita →
- 2A Jiang, Z Fu, W Sun e mais 3. Experimental and analytical studies of the effects of multiple lightning impulse currents on metal-oxide arrester blocks. 2014quem mais cita →
- 3KP Mardira, TK Saha e RA Sutton. Investigation of diagnostic techniques for metal oxide surge arresters. IEEE Trans Diel Elect Ins, 2005quem mais cita →
- 4J He, R Zeng, S Chen e mais 1. Thermal Characteristics of High-Voltage Whole-Solid-Insulated Polymeric ZnO Surge Arrester. IEEE Power Eng Rev, 2008quem mais cita →
- 5ZN Stojanović e ZM Stojković. Evaluation of MOSA condition using leakage current method. Int J Elec Pow Ener Syst, 2013quem mais cita →
- 6Y Fujiwara, Y Shibuya, M Imataki e mais 1. Evaluation of Surge Degradation of Metal Oxide Surge Arrester. IEEE Trans Power App Syst, 1982quem mais cita →
- 7S Tominaga, Y Shibuya, Y Fujiwara e mais 2. Stability and Long Term Degradation of Metal Oxide Surge Arresters. IEEE Trans Power App Syst, 1908quem mais cita →
- 8SM Seyyedbarzegar e M Mirzaie. Thermal balance diagram modelling of surge arrester for thermal stability analysis considering ZnO varistor degradation effect. IET Gener Transm Distrib, 2016quem mais cita →
- 9KL Chrzan. Influence of moisture and partial discharges on the degradation of high-voltage surge arresters. Euro. Trans Electr Power, 2004quem mais cita →
- 10VS Brito, GRS Lira, EG Costa e mais 1. A Wide-Range Model for Metal-Oxide Surge Arrester. IEEE Trans Power Del, 2018quem mais cita →
- 11EC Sakshaug. A brief history of AC surge arresters. IEEE Power Eng Rev, 1991quem mais cita →
- 12Z Abdul-Malek, N Yusoff e MF Mohd Yousof. Field experience on surge arrester condition monitoring - Modified Shifted Current Method. 2010quem mais cita →
- 13A Munir, Z Abdul-Malek e RN Arshad. Resistive component extraction of leakage current in metal oxide surge arrester: A hybrid method. Measurement, 2021quem mais cita →
- 14S Das, R Ghosh, S Dalai e mais 1. Study on the effect of moisture ingression into metal oxide surge arrester using leakage current analysis. 2017quem mais cita →
- 15VRN Barbosa, EG Costa, AF Leite Neto e mais 3. Evaluation of the metal oxide surge arresters degradation based on the loss tangent. 2021quem mais cita →
- 16TA Nogueira, C de Salles, ET Wanderley Neto e mais 1. Short duration current impulse waveform effects on the degradation and energy absorption capability of zinc oxide varistors. Elec Pow Syst Res, 2023quem mais cita →
- 17KS Ganesh. A Review of Zinc Oxide Varistors for Surge Arrester. 2018quem mais cita →
- 18JC Montenegro e JL Ramirez. Degradation of zinc oxide varistors. 1995quem mais cita →
- 19ABB. Blown Out Surge Arrester [Internet]. 2007quem mais cita →
- 20M Kan, S Nishiwaki, T Sato e mais 2. Surge Discharge Capability and Thermal Stability of a Metal Oxide Surge Arrester. IEEE Trans Power App Syst, 1983quem mais cita →
Quem cita esta obra
nenhum artigo do acervo cita esta obra — ainda
É sua obra?
Receba um aviso quando um artigo novo citar este trabalho.
também serve para acompanhar o autor que você estuda